I: An tun be 90% ka tansɔn na ani an ye “Snap” (flashover) mankan mɛn tanki kɔnɔ. Sisitɛmu y’a yɛrɛ sɛgɛsɛgɛ. Yala an ka ɲi ka GIS dayɛlɛ k’a labɛn sisan wa?

A: Wajibi tɛ. O be weele ko Yɛrɛ-Sɛgɛsɛgɛli.

"Saba -Baara" sariya (IEEE/IEC):

1. Strike 1: Ni flashover dɔ kɛra, i ka sisitɛmu bɔ ani ka kɔrɔbɔli daminɛ tugun.

2. Kɔlɔsili: Ni flashover filanan kɛra ni Voltage ye min ka bon ni fɔlɔ ta ye, o kɔrɔ ko kuran "jeni" burr fitinin dɔ, min ka ɲi, walima fɛn dɔ. GIS be to ka saniya.

3. Strike 2/3: Ni flashover kɛra Voltage kelen wala Lower Voltage la, i be ni gwɛlɛya sɔbɛ dɔ ye (isolateur faranin lo wala a ka boon lɔcogo tiɲɛna). AN KA kɔrɔbɔli lalɔ joona joona.

Kiiritigɛsoba: Flashover kelen min tugura o kɔ ni miniti 1 ye min be se ka minɛ ni tansɔn dafanin ye, o ka teli ka sɔn IEC 62271-203 ma.

An be se ka kɔrɔbɔli tansɔn sugandi cogo di "on-site" kɔrɔbɔli kama?

I: N ka GIS be 220 kV bɔ. Yala n’ ka ɲi k’a sɛgɛsɛgɛ ni tansɔn kelen ye min tun be izini kɔnɔ u ka Type Test wagati la wa?

A: ƆNƆƆN. Foro sɛgɛsɛgɛli tansɔnw ka dɔgɔ walisa ka "Over-stressing" minanw bali minw cira ka ban ani u minɛna ka ban.

"80% sariya":

1. Izini kɔrɔbɔli: GIS be kɔrɔbɔ dilanbaga fɛ 100% ka kɛɲɛ ni sariya ye (misali la, 460 kV 220 kV sisitɛmu kama).

2. Foro kɔrɔbɔli: An ka teli ka 80% lo kɛ izini ka kɔrɔbɔli fanga la (misali la, 368 kV).

3. A wagati: A ka ca a la, miniti 1 lo be kɛ 80% hakɛ la.

Mun na 80%? O ye balansi ye. A ka bon fɔɔ a be se ka fili dɔw sɔrɔ lajɛnba la wala ka bolifɛnw tiɲɛ, nka a ka dɔgɔ fɔɔ a tɛna kɛ sababu ye ka insulatɛriw kɔrɔbaya kudayi ni dafabaliya fitinin dɔ be yen.