Mun lo basiginin lo ka kɔrɔbɔli tansɔn sugandi AC Hipot kɔrɔbɔli kama?
Kɔrɔbɔli tansɔn be dantigɛ ni minanw ka insulasiyɔn hakɛ ye (Um, BIL) ani min be baara kɛ ni fɛɛnw ye - tansɔn kelen tɛ yen min be se ka mɔgɔw bɛɛ latanga.
Voltage sugandi ka kɛɲɛ ni minan suguya ye:
|
Minanw |
Dansiginin |
Sɛgɛsɛgɛli tansɔn |
Don hakɛ |
|
Fanga yɛlɛmalan (Um ka dɔgɔ ni 72,5 kV ye wala a ka kan n’o ye) |
IEC ka sariya 60076-300. |
1,7 × Um / √3 (min donna) + PD |
30 s ka kɔrɔbɔli + 5 min ka Um/√3. |
|
Fanga yɛlɛmalan (Um > 72,5 kV) |
IEC ka sariya 60076-300. |
1.7 × Um / √3 (waati surun-min donna) |
60 s |
|
Tilanyɔrɔ yɛlɛmalan |
IEC 60076-11 |
2.0 × tansɔn hakɛ |
60 s |
|
Kuran juru (MV) |
IEC ka sariya 60502-20. |
2.5 × U₀ |
Minutika 30 (sɔn) / miniti 60 (to) |
|
Kuran juru (HV) |
IEC 60840 |
2.0 × U₀ |
miniti 60 |
|
GIS / yɛlɛmalan |
IEC ka sariya 62271-1. |
1.2 × Um |
60 s |
|
Busi |
IEC 60137 |
1,2 × Um (PF kɔrɔbɔli) |
60 s |
|
CT/VT |
IEC ka sariya 61869-1. |
1,3–1,5 × Um/√3 (min be yɛlɛma) |
60 s |
Foro baara ɲɛyirali nafaman:
• Tuma o tuma, i ka tɔgɔ sɛbɛnin lajɛ (Um, BIL sɛbɛnin be yen).
• Ka tansɔn dɔgɔya ni 80% ye ka minan kɔrɔw sɛgɛsɛgɛ foro kɔnɔ (IEEE 400.2 ka juruw ta).
• I kana tɛmɛ tɔgɔla BIL kan abada.
• Aw ye fɛnw sariya sɛgɛsɛgɛ ka kɔn ka tansɔn - sugandi transformateur vs.