Q: N be nɛgɛdaga belebele dɔ ye min be ni bushings ye - sanfɛ min be sɛgɛsɛgɛri kɛ? Tuma juman lo n’ ka ɲi ka baara kɛ n’o ye sanni ka baara kɛ ni réacteur stack ye?
A: Ɔnhɔn - sɛgɛsɛgɛli yɛlɛmalan kɔrɔman ye yɛlɛmalan nɔgɔman ye min be yɛlɛma (220/380V kɔnɔ, 10–300 kV bɔ). Minɛn ɲuman min be se ka kɛ doni fitininw ye, minw ka setigiya man bon i n’a fɔ CTw, PTw, bushingw ani juru surunw (< 25 m).
Wagati min na i ka ɲi ka baara kɛ n’a ye:
|
I be kɔrɔbɔli kɛra... |
Seko |
Kɔrɔbɔli TX wa? |
Mun na? |
|
CT (sisan yɛlɛmalan) |
50–200 pF |
✅ A ka fisa |
Doni fitinin - TX b'a boli nɔgɔman na |
|
PT (fɛn min be se ka yɛlɛma) |
100-500 pF |
✅ A ka fisa |
O kuun kelen |
|
Bushing fitinin |
100-500 pF |
✅ A ka fisa |
Doni nɔgɔman |
|
Kabɔlɔ surun < 100 m |
< 20 nF |
✅ A ka ɲi |
Charge ka dɔgɔ kosɛbɛ |
|
GIS bay (circuit tigɛlan) |
5-50 nF |
✅ A sɔnna |
C hakɛlaman - OK ni dafɛla ye |
|
5 km kuran juru |
1 μF+ |
❌ Juguman |
Sisan belebeleba - lajɛ ɲiningali 5nan na |
|
Jeneratɛri statɔri |
1 μF+ |
❌ A ma ɲi . |
Gwɛlɛya kelen |
A sɔngɔ ɲɔgɔnna (kura, saan 2025):
50 kV / 5 kVA sɛgɛsɛgɛli TX: dɔrɔmɛ 8 000–15 000
100 kV / 10 kVA sɛgɛsɛgɛli TX: dɔrɔmɛ 20 000–40 000
200 kV / 50 kVA: dɔrɔmɛ 50,000+ - nka a ka ca; mɔgɔw be yɛlɛma ka taga SR la nivo nin na .
A be baara kɛ yɔrɔ minw na: Iziniw ka sɛgɛsɛgɛrikɛyɔrɔw (CT/PT/bushing mfr), yɛlɛmaniw kɛyɔrɔw, dilanyɔrɔ fitininw.